DTU111

60,0065,00

GPRS data logger with external 3dBi antenna and power supply from 3200 mAh battery. Designed for remote metering and monitoring applications. Device collects consumption data from pulse output meters and sensors, stores readings in non-volatile memory and transmits data to dispatching server over GPRS network. Suitable for water, gas, electricity metering.

Clear
Quick Order
SKU: DTU111 Categories: ,

GPRS data logger with external 3dBi antenna and power supply from 3200 mAh battery. Designed for remote metering and monitoring applications. Device collects consumption data from pulse output meters and sensors, stores readings in non-volatile memory and transmits data to dispatching server over GPRS network. Suitable for water, gas, electricity metering.

— 4 x pulse metering inputs
— 2 x signal inputs
— Configurable polling frequency: 2Hz/20Hz/100Hz
— Dual SIM card slots
— Autonomous operation from replaceable battery 3.6V 3200 mAh up to 4 years
— Data transmission over GPRS/TCP connection on a configurable schedule
— Sealed IP65 enclosure
— Easy local configuration via serial RS-232 port (or via mini-USB port using Serial-to-USB CDM10 Adapter)
— Remote configuration via free cloud platform iot24.eu web interface
— Free Cloud platform iot24.eu ensuring remote access to data via web interface
— External antenna 3dBi with cable

Options

DTU111, DTU111-Z (no power battery installed), DTU111.M (without enclosure), DTU111-Z.M (without battery & enclosure)

Specifications

 

SPECIFICATIONS
ENCLOSURE TYPE Type 1 (plastic, IP65)
Dimensions (L x W x H) 76 x 65 x 35 mm
NETWORK PARAMETERS
GSM GSM/GPRS 850/900/1800/1900. GPRS class 8/10/auto (up to 12) configurable. Rate (DL/UL): 85,6 kbps
IO PARAMETERS
GPIOs (IO1-IO4) x4 (configurable): pulse counter, signal input, leakage sensor, temperature sensor, NAMUR, 1-Wire, 4-20 mA current loop, load control, engine hours counter
Input Polling Frequency 2Hz: min. pulse duration – 500ms, max. pulse frequency at the input – 1Hz;
20Hz: min. pulse duration – 50ms, max. pulse frequency at the input – 10Hz
Input Conditions connected, disconnected, short circuit, break
Input Resistance Range 10 – 100 kOhm
Additional Input (IO5) x1 (configurable): signal input, leakage sensor
Additional Input (IO6) x1 (configurable): signal input, opening sensor
OTHER PORTS
Power Output x1: 3,6V
Serial Ports 1 x RS-232
Data Bit 7, 8
SIM 2 x mini-SIM
WM-Bus under development
POWER SUPPLY
Main power supply source Autonomous, LiSOCL2 3.6V battery, 3200 mAh
MECHANICAL & ENVIRONMENTAL
Weight 130 gr
Mounting wall
Operating temperature 10…+50°C
Warranty 2 years

Downloads

Documentation

Datasheet. ADGT DTU Data Logger Series. rev.1.1 (2020-12-21)
Declaration of Conformity. DTU GPRS Data Logger
DTU Remote Data Logger Series. Data Transmission Protocol. rev.1.7 (2020-11-27)

Ordering Information

Product Codes

PRODUCT CODE NETWORK TYPE ANTENNA/ANTENNA CONNECTOR
DTU1xx – plastic IP65 sealed case 76x65x35
DTU110 GPRS Internal 2-5.2dB flexible antenna
DTU111 GPRS External 3dB antenna
DTU117 GPRS External SMA(f) connector
DTU120 NB-IoT Internal 2-5.2dB flexible antenna
DTU121 NB-IoT External 3dB antenna
DTU127 NB-IoT External SMA(f) connector
DTU150 LTE Cat M1 Internal 2-5.2dB flexible antenna
DTU2xx – metal IP30 case 97x82x36
DTU217 GPRS External SMA(f) connector
DTU227 NB-IoT External SMA(f) connector
DTU257 LTE Cat M1 External SMA(f) connector
DTU287 GPRS/NB-IoT/Cat M1 External SMA(f) connector
DTU4xx – plastic IP65 sealed case 145x115x55
DTU413 GPRS Internal SMA(f) connector
DTU423 NB-IoT Internal SMA(f) connector
DTU453 LTE Cat M1 Internal SMA(f) connector
DTU483 GPRS/NB-IoT/Cat M1 Internal SMA(f) connector

Available Options

blank

Privacy Policy